On November 12, NOAA’s Climate Prediction Center kept its El Niño Advisory in place and put the chance of a strong-to-very-strong El Niño lasting through January–March 2027 at greater than 79%. California has been under a statewide state of emergency for El Niño preparedness since September 21.
The seasonal outlook points the same way. NOAA’s November 19 outlook for December through February gives better than a 40% chance of above-normal precipitation from southwestern Oregon and California east through the Southwest, and better than 60% in Southern California. An outlook shifts the odds. It does not promise a wet winter for any one site, and NOAA and the National Weather Service are clear that flooding can happen in any season and any year.
What a plant can control is whether its pumps work on the day the water arrives. Pumps that sat idle all summer are the ones most likely to fail in the first storm, and a dry afternoon is the cheapest time to find that out. This pre-storm pump inspection takes about an hour per pump station and needs no special tools beyond a clamp meter.
The pre-storm pump inspection: eight checks
- Run it wet. Fill the pit or wet well with water and watch a full cycle. The pump should start on its float or level control, pump down at a normal rate and shut off cleanly.
- Read the amps. While the pump runs, compare amp draw to the motor nameplate. Listen for grinding, rattling or cavitation.
- Clean the pit and free the floats. Sediment, leaves, trash and rags stick floats and clog impellers. Clear the pit, the intake screens and the grates upstream so water can reach the pump.
- Trip the high-level alarm. Then confirm that a person gets the call or text. An alarm nobody hears protects nothing.
- Check alternation. On duplex systems, confirm the controller alternates pumps and brings on the second pump when the first cannot keep up.
- Open the panel. Look for moisture, corrosion and loose connections.
- Walk the discharge line to its outlet. A crushed pipe or a buried outfall cuts capacity. Confirm each check valve is installed in the right direction and closes, so water does not run back into the pit and short-cycle the pump.
- Test backup power under load. Run the generator and transfer switch with the pumps on, top off the fuel, and confirm the generator can carry the starting current of every pump it is expected to run.
On larger submersibles, add two checks: look at the oil chamber and seal leak sensors (milky oil means water is getting past the mechanical seals), and run an insulation resistance test on the motor and cable.
What to add for your industry
Municipal water and wastewater
EPA’s lift station maintenance guidance calls for weekly inspection of light and alarm systems, monthly amp readings, and float cleaning and inspection four times a year. In California, a sewer spill of 1,000 gallons or more that reaches, or will probably reach, state waters must be called in to Cal OES within two hours of the operator learning of it. One action: clean the floats and test the alarms and auto-dialer at every station before the first big storm.
Manufacturing
The State Water Board told industrial permit holders on October 16 that all permit requirements remain in effect during El Niño, including stormwater samples taken within the first four hours of discharge from a qualifying storm. The same letter says unauthorized discharges will be evaluated for whether appropriate maintenance and preparation were done. One action: if your stormwater plan depends on a sump pump, run it wet and log the test with the date.
Food and beverage
Process wastewater and stormwater often share low ground at a plant. The quiet weeks after harvest and crush are a good window to pull, clean and test sump and wastewater pumps. One action: clear trench drains and catch basins at the same time as the pits, so water reaches the pump instead of the production floor.
Oil and gas
Containment areas and cellar sumps collect rain fast, and the pumps that empty them may not have run since last winter. One action: run every containment and sump pump through a full wet cycle, and check bearing housings and seal support systems for water before restarting equipment that has sat through a storm.
Agriculture
Well and booster pumps are idle between irrigation seasons, which makes winter the practical time to pull a pump for repair. Low-ground drainage pumps are the opposite: they work hardest in a wet winter. One action: test drainage pumps and stage fuel now, and schedule any well pump work while the pump is not needed.
If a check fails
Finding a seized pump, a failed check valve or a generator that will not carry the load is the point of the walkdown. Repair shops fill up once storms start, because every facility in a region tends to need help in the same week. A problem found in November or December still has time to be fixed.
Related: Is Your Facility Ready for El Niño? A Pump Preparedness Checklist for California. DXP Pacific service centers: Northern California, Central California, Southern California and Southern Nevada.
Pre-Storm Pump Inspection
DXP Pacific service teams in California and Nevada can walk your pump stations with you, test each pump and give you a written list of what to fix before the rain.
Request an inspection(866) 472-3959Sources
- NOAA Climate Prediction Center, ENSO Diagnostic Discussion, November 12, 2026
- NOAA Climate Prediction Center, seasonal outlook discussion, November 19, 2026
- Office of the Governor of California, state of emergency for El Niño preparedness, September 21, 2026
- National Weather Service and CNAP, El Niño in California and Nevada, December 2015
- U.S. EPA, Collections and Lift Station Maintenance: Reducing the Risks for Sanitary Sewer Overflows, July 2023
- State Water Resources Control Board, Order WQ 2022-0103-DWQ, Attachment E1
- State Water Resources Control Board, Industrial Facility Preparation for the Historic El Niño Event, October 16, 2026